Electrical

NBR 5410 ampacity correction (derating) factors

The complete set of NBR 5410 ampacity correction factors — ambient and soil temperature, circuit grouping by physical arrangement, multiple layers, soil thermal resistivity, burial depth and the 4-loaded-conductor factor — as applied by the LOGOS cable-sizing engine.

Why the table ampacity is never the final answer

The NBR 5410 ampacity tables assume a reference world: 30 °C air (or 20 °C soil), one circuit alone, soil at 2.5 K·m/W, burial at 0.70 m. Every real installation deviates from at least one of these, and the deviation is corrected by multiplying factors:

Iz' = Iz(table) × Ft × Fa (× Fs × Fp when buried)

The corrected Iz′ is what must exceed the design current Ib and coordinate with the protective device rating. Skipping a factor does not fail loudly — it ships a cable that runs hot for years.

The factors in this page

  • Ft — temperature (Table 40). Two bases, often confused: 30 °C for lines in air, 20 °C for buried lines. Applying the air column to a buried duct at 30 °C soil flatters the result by ~8% — in the unsafe direction.
  • Fa — grouping (Table 42). Depends on the physical arrangement, not just the circuit count: a bundle in conduit derates far more than a single layer on a perforated tray.
  • Multilayer (Table 43). Stacked layers on trays derate drastically — two layers of two circuits already fall to 0.68 against 0.88 of a single layer.
  • Fs — soil resistivity (Table 41). The tables assume a conservative 2.5 K·m/W; measured wet soil near 1.0 releases up to +50% on directly buried cables.
  • Fp — depth. Below the reference 0.70 m, roughly −1% per extra 10 cm (down to ~2 m).
  • 4 loaded conductors. With 3rd-harmonic content above 33% the neutral counts as loaded and a 0.86 factor applies.

A worked micro-example

A 70 mm² XLPE copper cable, method E (perforated tray), 40 °C ambient, 4 circuits in a single layer: Iz table = 246 A; Ft = 0.91; Fa = 0.77. Iz′ = 246 × 0.91 × 0.77 ≈ 172 A — 30% below the table value. This is the difference between a cable that meets Ib = 180 A on paper and one that actually does.

Temperature factor Ft — in air, base 30 °C (NBR 5410 Table 40)

Ambient (°C)EPR/XLPE 90 °CPVC 70 °C
101.151.22
151.121.17
201.081.12
251.041.06
3011
350.960.94
400.910.87
450.870.79
500.820.71
550.760.61
600.710.5
650.65
700.58

Temperature factor Ft — buried lines, base 20 °C soil (NBR 5410 Table 40)

Soil temperature (°C)EPR/XLPE 90 °CPVC 70 °C
101.071.1
151.041.05
2011
250.960.95
300.930.89
350.890.84
400.850.77
450.80.71
500.760.63
550.710.55
600.650.45
650.6
700.53
750.46
800.38

Grouping factor Fa by number of circuits and arrangement (NBR 5410 Table 42)

CircuitsBundle / enclosed conduitSingle layer on wall (method C)Single layer, perforated tray (E/F)
1111
20.80.850.88
30.70.790.82
40.650.750.77
50.60.730.75
60.570.720.73
70.540.720.73
80.520.710.72
90.50.70.72
120.45
160.41
200.38

Above the last tabulated count, keep the last factor. Layers beyond one: see the multilayer table below.

Multilayer grouping factor (NBR 5410 Table 43) — methods C, E, F

Layers2 circ./layer3 circ./layer4 circ./layer6 circ./layer9 circ./layer
20.680.620.60.580.56
30.620.570.550.530.51
40.60.550.520.510.49
60.580.530.510.490.48
90.560.510.490.480.46

Soil thermal resistivity factor (NBR 5410 Table 41) — base 2.5 K·m/W

Resistivity (K·m/W)Cables in buried ductDirectly buried cables
0.51.281.88
0.71.21.62
11.181.5
1.51.11.28
21.051.12
2.511
30.960.9

Standards & methods

  • ABNT NBR 5410 (Tables 40–43, 6.2.5)
  • IEC 60364-5-52

Frequently asked questions

In which order do I apply the factors?

They multiply — order does not matter: Iz′ = Iz(table) × Ft × Fa, plus soil resistivity and depth factors for buried lines. The corrected Iz′ must be ≥ the design current Ib (and coordinate with the protection device).

Which grouping column applies to cables on a perforated tray?

The single-layer perforated-tray column (methods E/F). Using the bundle/conduit column (0.57 at 6 circuits vs the correct 0.73) over-derates by ~28% and buys copper you do not need. If the cables are stacked in more than one layer, switch to the multilayer table — it is much more severe.

My buried line is deeper than 0.70 m. Does it matter?

Yes, slightly: NBR 5410 tables assume 0.70 m. As a practical rule, capacity drops about 1% per additional 10 cm, valid down to about 2 m. At 1.5 m that is ≈ 8% — often the difference of one section step on long feeders.

When does soil thermal resistivity help instead of hurt?

The tables assume a conservative 2.5 K·m/W. Wet, compacted soil around 1.0 K·m/W raises the capacity of a directly buried cable by up to 50% — the single most powerful lever in buried-line design. It requires a measured value, not a guess.

Do the factors apply to the neutral too?

The factors correct the circuit as a whole. What changes with the neutral is the count of loaded conductors: with 3rd-harmonic content above 33% the neutral becomes a loaded conductor and an additional 0.86 factor applies on the 3-conductor ampacity.

Use these values in a calculator

More reference tables