Capacitor bank sizing: reactive power, stages and protection for power factor correction
Sizing a capacitor bank means computing the reactive power kVAr needed to raise the power factor from its current to its target value, then splitting that power into commercial stages and selecting the capacitor, contactor, fuse and (where needed) the detuning reactor for each one.
When to use
Use it whenever an installation draws a low (lagging) power factor and you need to compensate it at the point of common coupling, at a switchboard or at a motor: avoiding the utility's reactive-energy surcharge, freeing transformer and cable capacity, and improving voltage regulation. The method is the heart of every power factor correction project — it sets how many kVAr to install, whether to use a fixed bank or an automatic (multi-stage) one, and it sizes the switching and protection of each stage. It is also the tool to verify an existing bank that overcorrects, trips on inrush or excites a harmonic resonance with the supply.
What capacitor bank sizing is
Sizing a capacitor bank is not picking a kVAr value from a catalogue and bolting it to the busbar: it is computing exactly how much reactive power an installation needs to raise its power factor from the present value to the target, then deciding how to deliver that power — as one fixed block or as several switchable stages — and how to protect and switch each block safely. The number that starts everything is the reactive power Qc; everything downstream (stages, currents, contactors, fuses, reactors, the enclosure) follows from it.
The most common field mistake is to treat power factor correction as a single number bought once. In a real plant the load breathes through the day, the network carries harmonics, and the capacitor itself draws a violent inrush every time it switches. A correct design accounts for all three.
The reactive power to install
A load that draws active power P at a lagging power factor fp₁ also draws reactive power q₁ = P·tan φ₁. To raise the power factor to fp₂ you must supply the difference locally:
Qc = P · (tan φ₁ − tan φ₂)
Here φ₁ = acos(fp₁) and φ₂ = acos(fp₂). Because a capacitor can only add capacitive reactive power, the target fp₂ must be greater than fp₁ — asking for a lower target is physically impossible and the method flags it instead of silently returning a “minimum bank”. The computed Qc is then rounded up to the nearest commercial bank value (the 2.5 / 5 / 7.5 / 10 / 12.5 / 15 / 20 / 25 / 30 / 40 / 50 … kVAr series), giving Qbank.
The obtained power factor is checked against the residual reactive power q₂ = q₁ − Qbank:
fp_obtained = P / √(P² + q₂²)
This confirms the rounded bank actually clears the target with a small margin rather than over- or under-correcting.
Fixed bank or automatic bank
A fixed bank is a single block, sensible only when the load is stable (an individual motor switched with its starter). When the load varies, a fixed bank overcorrects at light load and produces a leading power factor — itself penalised. The answer is an automatic bank: the total Qbank is split into stages that a power factor controller switches in and out to track the target.
The stages can follow two schemes:
- Equal — every stage carries the same kVAr (step = Qbank/N). Simple, robust, the default.
- Binary — stage weights follow 1 : 2 : 4 : … : 2^(N−1), so the smallest step is Qbank/(2^N − 1). Three binary stages (1+2+4) resolve in seven levels what would need seven equal stages — finer regulation with fewer contactors, at the cost of unequal hardware.
Current, contactor and fuse per stage
Each stage of Q_stage kVAr at line voltage V draws a rated three-phase current:
Icn = Q_stage · 1000 / (√3 · V)
But a capacitor is never sized for Icn. IEC 60831 combines a 1.10 overvoltage with a 1.30 factor for harmonics and capacitance tolerance, giving the sizing current:
Ic_dim = 1.43 · Icn
That is the current the cable and the general protection must carry. The per-stage switching and protection follow commercial rules:
- Contactor ≥ 1.5·Icn, in utilization category AC-6b, fitted with pre-charge resistors to tame the capacitor inrush;
- gG fuse ≈ 1.65·Icn, rounded up to the standard fuse series.
A general AC-3 motor contactor is the wrong tool here — the repeated capacitor inrush welds its contacts.
The detuning reactor and harmonics
On a clean network an undetuned bank is fine. On a network rich in harmonics — variable-speed drives, rectifiers, UPS — the bank and the supply inductance form a parallel resonance at order:
h_r = √(Scc / Qc), with Scc = √3·V·Icc
If h_r lands in the danger band (roughly 4.5 to 7.5, i.e. near the 5th or 7th harmonic), the bank amplifies that harmonic and capacitors and fuses fail early. The cure is a detuning reactor in series with each stage, sized so the series LC tunes below the lowest troublesome harmonic at order:
n = 1 / √p
For the common p = 7 %, n ≈ 3.78 — comfortably below the 5th. The reactor inductance per phase is L = XL/ω with XL = p·Xc and Xc = V²/Q_stage. The reactor, however, raises the voltage across the capacitor to:
Vc = V / (1 − p)
so the capacitor units must be rated above the line voltage (for 380 V at 7 %, Vc ≈ 409 V). Forgetting this is a classic cause of premature capacitor failure in detuned banks.
How the method assembles the bank
The calculation proceeds in steps:
- Reactive power — from P, fp₁ and fp₂ it computes Qc and rounds up to the commercial Qbank, then checks the obtained power factor.
- Stages — for a fixed bank, one stage; for an automatic bank, N stages with equal or binary weights, and the smallest switching step.
- Per stage — it sizes the commercial capacitor unit, the rated and sizing currents (1.43·Icn), the AC-6b contactor (1.5·Icn), the gG fuse (1.65·Icn) and, if detuned, the reactor inductance and the elevated capacitor voltage.
- Overall — it sums the currents to set the general protection (1.43·Ic_total) and verifies the assembly’s short-circuit withstand against Icc; it estimates the equivalent capacitance and the resonance order.
- Enclosure — it lays the stages, controller and general device into a cabinet (à la motor control centre), returning the build dimensions for the 2D/3D drawing.
Practical design notes
- Aim for 0.92–0.95, not unity, and prefer an automatic controller so light load does not push you into a leading power factor.
- Size everything for 1.43·Icn, per IEC 60831, not for the rated current.
- Use AC-6b contactors with pre-charge — never a plain motor contactor on a capacitor.
- Detune (5.67 / 7 / 14 %) whenever the network carries harmonics, and rate the capacitors for Vc = V/(1 − p).
- Check the parallel resonance h_r = √(Scc/Qc) before committing to an undetuned bank.
Following this chain — reactive power, stages, per-stage current and protection, detuning and resonance check, then the assembly — yields a capacitor bank that meets the target power factor, survives switching and harmonics, and matches the field-validated reference sheet.
Formulas and fundamentals
Qc = P · (tan φ₁ − tan φ₂) Reactive power the bank must supply. P is the active power [kW], φ₁ = acos(fp₁) the current displacement angle and φ₂ = acos(fp₂) the target angle. Because a capacitor only raises the power factor, the target fp must be greater than the current fp; otherwise the correction is physically impossible.
step = Qbank / Σweights ; Q_stage = step · weight The commercial bank Qbank is split into N stages. For equal stages every weight is 1 (step = Qbank/N). For a binary scheme the weights are 1:2:4…2^(N-1), so the smallest step equals Qbank/(2^N − 1), giving finer regulation with fewer contactors.
Icn = Q_stage·1000 / (√3·V) ; Ic_dim = 1.43·Icn Icn is the rated three-phase current of the stage [A], with V the line voltage [V]. IEC 60831 requires sizing for 1.43·Icn (overvoltage 1.10 × harmonic/tolerance 1.30) — that current drives the cable, the contactor and the general protection.
contactor ≥ 1.5·Icn (AC-6b) ; fuse ≈ 1.65·Icn (gG) The capacitor contactor (AC-6b, with pre-charge resistors for inrush) is chosen for at least 1.5·Icn; the gG fuse for about 1.65·Icn, rounded up to the commercial series. Both must tolerate the transient charging current.
Xc = V²/Q_stage ; XL = p·Xc ; L = XL/ω ; Vc = V/(1 − p) For a detuned bank, p is the detuning factor (e.g. 7 %). The reactor inductance L [H] is set so the series LC tuning order n = 1/√p (≈ 3.8 for 7 %) sits below the lowest troublesome harmonic. The capacitor sees an elevated voltage Vc = V/(1 − p), which must be respected when rating the units.
h_r = √(Scc / Qc) Order of the parallel resonance between the bank and the supply, with Scc = √3·V·Icc the short-circuit power. If h_r lands near a strong harmonic (typically 5th or 7th) on an undetuned bank, the bank amplifies that harmonic — a detuning reactor shifts the tuning safely below it.
Standards & methods
- IEC 60831-1/-2 — Shunt power capacitors of the self-healing type for a.c. systems (Un ≤ 1000 V)
- ABNT NBR IEC 60831 — Brazilian adoption of IEC 60831
- IEC 60439 / IEC 61439 — Low-voltage switchgear and controlgear assemblies
- IEC 61921 — Power capacitors: low-voltage power factor correction banks
- IEEE 519 — Harmonic control in electric power systems
- IEC 60947-4-1 (utilization category AC-6b) — Capacitor switching contactors
Typical reference values
| Quantity | Typical range | Note |
|---|---|---|
| Target power factor | 0.92 to 0.95 | Most utilities require fp ≥ 0.92; 0.95 leaves a margin against load variation. |
| Detuning factor (p) | 5.67 %, 7 % or 14 % | 7 % (tuning order ≈ 3.8) is the most common where 5th/7th harmonics dominate. |
| Sizing factor (IEC 60831) | Ic_dim = 1.43·Icn | Covers 1.10 overvoltage × 1.30 harmonic and manufacturing tolerance. |
| Contactor / fuse | ≥ 1.5·Icn / ≈ 1.65·Icn | AC-6b contactor with pre-charge; gG fuse for the charging transient. |
| Number of automatic stages | 4 to 12 | More stages give finer regulation; a binary scheme reaches the same with fewer. |
| Resonance danger zone (undetuned) | 4.5 ≤ h_r ≤ 7.5 | If the parallel resonance lands here, add a detuning reactor. |
Worked example
Automatic bank on a 250 kW industrial switchboard
Inputs
- Active power
- P = 250 kW
- Current power factor
- fp₁ = 0.78 —
- Target power factor
- fp₂ = 0.95 —
- Line voltage
- V = 380 V
- Scheme
- 3 equal stages, detuned 7 % —
- Short-circuit current
- Icc = 25 kA
Results
- Required reactive power
- Qc ≈ 118.4 kVAr
- Commercial bank adopted
- Qbank = 125 kVAr
- Obtained power factor
- fp ≈ 0.957 —
- Stage current / sizing current
- Icn ≈ 63.3 / Ic_dim ≈ 90.6 A
- Contactor / gG fuse per stage
- 95 / 125 A
- General protection
- 315 A
- Capacitor voltage (detuned)
- Vc ≈ 409 V
With tan φ₁ = 0.802 (fp 0.78) and tan φ₂ = 0.329 (fp 0.95), the required reactive power is Qc = 250·(0.802 − 0.329) ≈ 118.4 kVAr, rounded up to the commercial 125 kVAr. The residual reactive becomes q₂ = 200.5 − 125 ≈ 75.5 kVAr, so the obtained power factor settles at fp = 250/√(250² + 75.5²) ≈ 0.957 — just above the 0.95 target with a small margin. Split into 3 equal stages, each stage is 125/3 ≈ 41.7 kVAr with Icn ≈ 63.3 A; sizing at 1.43·Icn ≈ 90.6 A drives a 95 A AC-6b contactor and a 125 A gG fuse, while the total Ic_dim ≈ 271 A sets a 315 A general protection. The 7 % detuning reactor tunes the bank at order n = 1/√0.07 ≈ 3.78 — safely below the 5th harmonic — and raises the capacitor voltage to Vc = 380/0.93 ≈ 409 V, which is why the units must be rated above the line voltage.
Common mistakes
- Setting a target power factor below the current one — a capacitor can only raise the power factor, so the request is physically impossible and yields zero correction.
- Sizing the contactor and cable for the rated current Icn instead of 1.43·Icn, ignoring the IEC 60831 derating for overvoltage and harmonics.
- Installing an undetuned bank on a network rich in 5th/7th harmonics, where the parallel resonance is amplified and capacitors and fuses fail prematurely.
- Using a general-purpose AC-3 contactor instead of an AC-6b with pre-charge resistors — the capacitor inrush welds the contacts.
- Forgetting that the detuning reactor raises the capacitor voltage to V/(1 − p); rating the units for V leads to overstress.
- Overcorrecting to fp = 1 or beyond at light load, causing a leading power factor and a voltage rise that the utility also penalizes.
Frequently asked questions
How much reactive power do I need to correct the power factor?
The required reactive power is Qc = P·(tan φ₁ − tan φ₂), where φ₁ = acos(current fp) and φ₂ = acos(target fp). For example, 250 kW from fp 0.78 to 0.95 needs about 118 kVAr, which is then rounded up to the nearest commercial bank (125 kVAr). The active power P stays the same; only the reactive component is reduced.
When should I use an automatic (multi-stage) bank instead of a fixed one?
Use a fixed bank for a stable, near-constant load (for instance an individual motor). Use an automatic bank with several stages and a power factor controller when the load varies through the day: the controller switches stages in and out to track the target without overcorrecting at light load. A binary scheme (weights 1:2:4) reaches the same resolution with fewer stages than equal steps.
What is a detuning reactor and when is it required?
A detuning reactor is an inductor placed in series with each capacitor stage so the series LC tunes at an order n = 1/√p below the lowest dominant harmonic (n ≈ 3.8 for 7 %). It is required when the network is rich in harmonics (variable-speed drives, rectifiers) and the bank's parallel resonance h_r = √(Scc/Qc) would otherwise land near the 5th or 7th harmonic and be amplified. The reactor also raises the capacitor voltage to V/(1 − p).
Why size the capacitor current at 1.43·Icn?
IEC 60831 requires capacitors to withstand 1.10 times the rated voltage and to carry harmonic currents, plus a manufacturing tolerance on capacitance. Combined, these give a current factor of about 1.43·Icn. Cables, contactors and the general protection must be sized for that current, not for the rated Icn, or they will be undersized in service.
Why use an AC-6b contactor and not an ordinary one?
Switching a capacitor produces a very high, short inrush current (tens of times the rated current). A capacitor-switching contactor in utilization category AC-6b includes pre-charge resistors that limit this transient and protect the main contacts from welding. A general AC-3 motor contactor would degrade quickly under repeated capacitor inrush.
Can I correct all the way to power factor 1.0?
It is not recommended. Targeting unity (or a fixed bank that stays on at light load) can overcorrect and produce a leading power factor, raising the voltage and tripping the utility's reactive-energy penalty in the other direction. A target of 0.92 to 0.95 with an automatic controller keeps a safe margin against load variation.
Glossary
- Power factor (fp)
- Ratio of active power to apparent power, fp = P/S = cos φ. A low (lagging) fp means a large reactive component drawn from the supply.
- Reactive power (kVAr)
- The non-working power exchanged with inductive loads. A capacitor bank supplies it locally so the supply does not have to.
- Stage
- A switchable block of capacitors within an automatic bank, controlled independently by the power factor controller to track the target.
- Detuning factor (p)
- The percentage by which a series reactor detunes a capacitor stage (5.67 %, 7 % or 14 %), tuning the LC at order 1/√p below the lowest harmonic.
- AC-6b
- IEC 60947 utilization category for contactors that switch capacitor banks, fitted with pre-charge resistors to handle the inrush.
- gG fuse
- Low-voltage general-purpose fuse-link (full-range) used to protect each capacitor stage against short circuits.
- Parallel resonance (h_r)
- The harmonic order h_r = √(Scc/Qc) at which the bank and the supply inductance resonate; near a strong harmonic it amplifies distortion.