SPD sizing: Type, Uc, Up and coordination Up ≤ Uw
Sizing a surge protective device (SPD) means choosing the right test class (Type 1/2/3) and continuous operating voltage Uc for the earthing system, then proving that the effective protection level Up plus the connection-lead drop stays below the equipment withstand voltage Uw.
When to use
Use it whenever you specify surge protection for a low-voltage installation: the service entrance, distribution boards, or right next to sensitive electronics. SPD selection is the step that links the lightning/overvoltage risk to the equipment it protects — it sets the Type from the position and the presence of an LPS or overhead line, fixes Uc from the earthing arrangement so the SPD does not age prematurely, and verifies the coordination Up_effective ≤ Uw so the protected equipment actually survives a surge. It is also the tool to diagnose a board where SPDs fail repeatedly, almost always because Uc was too low for the earthing system or the connection leads were too long.
What SPD sizing is
Sizing a surge protective device is not picking the highest-current model in the catalog: it is matching three voltages so that a transient overvoltage is clamped to a level the protected equipment can survive, while the device itself lives a long life on the system. Those three voltages are Uc (what the SPD must permanently tolerate), Up (what it lets through during a surge), and Uw (what the equipment can withstand). Get the relationship between them right and the installation is protected; get it wrong and either the SPD ages and fails, or the surge passes through to the equipment.
The most common field failure is an SPD that “burns out for no reason” — almost always because its Uc was chosen equal to the nominal voltage instead of above the real permanent stress, or because the connection leads were so long that the effective protection level climbed past the equipment withstand.
Continuous operating voltage Uc — set by the earthing
The first decision is Uc, the voltage the SPD endures continuously without conducting. It is governed by the earthing system, per IEC 60364-5-534:
- TN-S, TN-C-S, TN-C: the line-to-neutral mode sees up to 1.1·Uo, so Uc must be at least 1.1·Uo.
- TT (SPD line-to-PE, 3+1 arrangement): the L-PE SPD must withstand a temporary overvoltage from an upstream fault, so Uc must be at least 1.55·Uo — markedly higher than the TN value.
- IT (without distributed neutral): a first earth fault is not cleared and the healthy phases rise toward the line-to-line voltage, so the SPD must withstand √3·Uo.
The required value is then rounded up to the next commercial Uc in the standard series (150, 275, 320, 335, 350, 385, 420, 440, 460, 550, 690 V). For a 230 V system this lands on 275 V in TN, 385 V in TT (1.55·230 ≈ 357 V), and about 420-440 V in IT. Choosing Uc too low is the textbook cause of premature SPD ageing.
Equipment withstand voltage Uw — by overvoltage category
The target the SPD has to beat is Uw, the rated impulse withstand voltage of the equipment it protects. IEC 60364-4-44 (Table 443.2) assigns it by overvoltage category and voltage band:
| Category | Where | Uw (230/400 V) |
|---|---|---|
| IV | Origin / service entrance | 6 kV |
| III | Distribution (boards, fixed wiring) | 4 kV |
| II | Utilization (appliances, tools) | 2.5 kV |
| I | Sensitive electronics | 1.5 kV |
The 120-240 V band uses lower values (4 / 2.5 / 1.5 / 0.8 kV). The category descends as you move from the origin toward the load, which is exactly why protection is staged: a Type 1 at the entrance brings the surge down, and a downstream Type 2/3 brings it under the lower Uw of the sensitive load.
The effective protection level — Up is not enough
The datasheet Up is measured at the SPD terminals, but the equipment is connected through leads. During a fast surge the inductance of those leads produces an extra voltage of roughly 1 kV per metre of connection (phase + PE). The voltage the equipment really sees is therefore:
Up_effective = Up + ΔU, with ΔU ≈ 1 kV/m · L_conn
This is why the connection must be kept ≤ 0.5 m: a careless 1 m loop turns a 1.5 kV SPD into 2.5 kV effective, enough to break coordination with a Category III (4 kV) board and certainly with a Category I (1.5 kV) load. A short, V-shaped connection is one of the cheapest ways to improve protection.
The coordination condition
Everything converges on a single inequality. The SPD coordinates with the equipment only when:
Up_effective ≤ Uw
and good practice adds a 20 % reserve to absorb ageing, tolerance and oscillation:
Up_effective ≤ 0.8·Uw
Rearranged, the largest SPD Up that still gives the 20 % margin is Up_max = 0.8·Uw − ΔU. If the effective level sits between 0.8·Uw and Uw, the device still protects but with little headroom — the cue to pick a lower-Up SPD, shorten the leads, or add a Type 3 stage near the load.
Choosing the Type — position and lightning exposure
The SPD Type (test class) follows from where it sits and whether a direct lightning current can reach it:
- Service entrance, with an LPS or exposed overhead line → Type 1, tested with the 10/350 µs impulse current Iimp (12.5 kA/pole for LPL III/IV, 25 kA/pole for LPL I/II, from the IEC 62305-2 / NBR 5419-2 risk study). Only a Type 1 drains a direct lightning current; a Type 2/3 in that position fails on the first strike.
- Entrance or distribution board, no direct-strike exposure → Type 2, tested with the 8/20 µs currents In (repetitive nominal) and Imax (single peak). This is the workhorse of the boards.
- Next to sensitive equipment (≤ 10 m) → Type 3, fine protection, always downstream of a Type 1/2 and never alone at the origin.
A common, invalid combination the method flags as an error: a non-Type-1 SPD at an entrance with an LPS, or a Type 3 placed at the origin.
Short-circuit withstand and backup
A surge protective device also has to survive the power-frequency fault that may follow. Its short-circuit current rating Isccr must be at least the prospective fault current Icc at the installation point, and this rating is only valid together with the manufacturer-specified backup protection (gG fuse or breaker). The connection lead is sized at 6 mm² Cu for a Type 2 and 16 mm² Cu for a Type 1. Take Icc from the short-circuit study; without it, Isccr and the backup cannot be verified.
Practical design considerations
- Pin Uc to the earthing first: 1.1·Uo for TN (L-N), 1.55·Uo for TT (L-PE), √3·Uo for IT, rounded up to a commercial value.
- Read Uw from the category: IV at the origin, III at boards, II/I toward the load — and remember the voltage band.
- Never compare bare Up with Uw: add the lead drop and keep the connection ≤ 0.5 m.
- Aim for the 20 % margin: Up_effective ≤ 0.8·Uw leaves room for ageing.
- Match the Type to the position: Type 1 only where direct lightning can reach; Type 3 only near the load.
- Verify Isccr ≥ Icc with the specified backup.
Following this chain — Uc from the earthing, Uw from the category, the Type from the position, then the coordination Up_effective ≤ Uw and the short-circuit check — yields an SPD selection that protects the equipment and survives the system it sits on.
Formulas and fundamentals
Uc ≥ 1.1·Uo (TN) ; Uc ≥ 1.55·Uo (TT, L-PE) ; Uc ≥ √3·Uo (IT without neutral) Minimum Uc the SPD must permanently withstand without conducting, set by the earthing system (IEC 60364-5-534). Uo is the line-to-earth voltage of the system [V]. In TN the L-N mode sees 1.1·Uo; in TT, the L-PE SPD (3+1 arrangement) must withstand 1.55·Uo because a fault upstream can raise the L-PE voltage; in IT, a healthy first fault can raise the voltage to √3·Uo. The adopted Uc is the next commercial value ≥ the requirement.
Uw = f(overvoltage category, voltage band) Rated impulse withstand voltage of the protected equipment, from IEC 60364-4-44 Table 443.2. For the 230/400 V band: Category IV (origin) = 6 kV, III (distribution) = 4 kV, II (appliances) = 2.5 kV, I (sensitive electronics) = 1.5 kV. The 120-240 V band uses lower values (4 / 2.5 / 1.5 / 0.8 kV).
ΔU = 1 kV/m · L_conn Inductive voltage rise across the SPD connection leads during the surge. L_conn is the total length of the phase and PE leads [m]. The 1 kV/m rule of thumb (IEC 61643-12) is why leads must be kept ≤ 0.5 m: long leads add directly to the protection level seen by the equipment.
Up_eff = Up_dps + ΔU The voltage actually let through to the equipment terminals: the SPD voltage protection level Up from the datasheet plus the lead drop ΔU. This — not the bare Up — is what must be compared with Uw.
Up_eff ≤ Uw (ideally Up_eff ≤ 0.8·Uw) The SPD coordinates with the equipment only if the effective protection level stays below the withstand voltage. A 20 % margin (Up_eff ≤ 0.8·Uw) is recommended to cover ageing, manufacturing tolerance and oscillation. The maximum SPD Up that still gives 20 % margin is Up_max = 0.8·Uw − ΔU.
Isccr ≥ Icc (with backup protection) The SPD short-circuit current rating Isccr must be at least the prospective fault current Icc at the installation point [kA], guaranteed together with the manufacturer-specified backup device (gG fuse or breaker). Icc comes from the short-circuit study.
Standards & methods
- IEC 61643-11 — Low-voltage surge protective devices: requirements and test methods
- IEC 61643-12 — SPD selection and application principles (Up, ΔU, coordination)
- IEC 60364-5-534 — Selection and erection: devices for protection against transient overvoltages
- IEC 60364-4-44 (Table 443.2) — Protection against voltage disturbances; rated impulse withstand voltage Uw
- ABNT NBR 5410 (6.3.5) — Low-voltage electrical installations: surge protection
- IEC 62305-2 / ABNT NBR 5419-2 — Lightning protection risk management (LPL → Iimp)
Typical reference values
| Quantity | Typical range | Note |
|---|---|---|
| Uc — TN (L-N), Uo = 230 V | ≥ 253 V → 275 V | 1.1·Uo rounded up to the commercial series (150/275/320/385/440 V). |
| Uc — TT (L-PE, 3+1), Uo = 230 V | ≥ 357 V → 385 V | 1.55·Uo: the TT L-PE SPD must withstand the temporary overvoltage from an upstream fault. |
| Uc — IT, Uo = 230 V | ≥ 398 V → 420/440 V | √3·Uo, because a first earth fault raises the voltage on healthy phases. |
| Uw — 230/400 V band | Cat IV 6 / III 4 / II 2.5 / I 1.5 kV | IEC 60364-4-44 Table 443.2; the 120-240 V band is lower. |
| Connection-lead length | ≤ 0.5 m | Each metre adds ~1 kV to the effective Up — the most common coordination killer. |
| Type 1 impulse current Iimp (10/350) | 12.5 to 25 kA/pole | 12.5 kA for LPL III/IV, 25 kA for LPL I/II (from the risk study). |
| Type 2 nominal current In (8/20) | In 5-20 kA · Imax 15-70 kA | In is the repetitive service value; Imax the single peak it withstands. |
Worked example
Type 2 SPD at a 230/400 V TN-S distribution board
Inputs
- Line-to-earth voltage (Uo)
- Uo = 230 V
- Earthing system
- TN-S —
- Overvoltage category (equipment)
- Category III —
- SPD voltage protection level (Up)
- Up = 1.5 kV
- Connection-lead length
- L = 0.5 m
- Prospective fault current (Icc)
- Icc = 10 kA
Results
- Required Uc
- Uc ≥ 253 V
- Adopted Uc (commercial)
- 275 V
- Equipment withstand (Uw)
- Uw = 4.0 kV
- Connection drop (ΔU)
- ΔU = 0.5 kV
- Effective protection level
- Up_eff = 2.0 kV
- Max SPD Up for 20 % margin
- Up_max = 2.7 kV
- Required Isccr
- Isccr ≥ 10 kA
Required Uc is 1.1·230 ≈ 253 V, rounded up to the commercial 275 V — comfortably above the permanent L-PE stress so the SPD does not age. For Category III in the 230/400 V band, Uw = 4 kV. The connection leads add ΔU = 1 kV/m · 0.5 m = 0.5 kV, so the effective protection level is Up_eff = 1.5 + 0.5 = 2.0 kV, well below the 4 kV withstand: the SPD coordinates. It also clears the 20 % rule (2.0 kV ≤ 0.8·4 = 3.2 kV), and any SPD with Up ≤ Up_max = 0.8·4 − 0.5 = 2.7 kV would still coordinate with margin. With Icc = 10 kA, the SPD must have Isccr ≥ 10 kA backed by the manufacturer-specified gG fuse or breaker, and a Type 2 device uses a 6 mm² Cu connection lead.
Common mistakes
- Choosing Uc equal to or below Uo: in TN the SPD permanently sees ~1.1·Uo (≥ 275 V on a 230 V system), and in TT the L-PE SPD must withstand 1.55·Uo (≥ 385 V) — too low a Uc ages and fails.
- Using a Type 2 or Type 3 SPD at the service entrance when an LPS or overhead line is present: only a Type 1 (Iimp 10/350) withstands the direct lightning current; the others fail on the first strike.
- Installing a Type 3 SPD at the origin: Type 3 is fine protection for near the load (≤ 10 m), never at the entrance.
- Comparing the bare datasheet Up with Uw and forgetting the connection-lead drop — long leads can push Up_effective above Uw even when the SPD looks adequate.
- Ignoring Isccr: an SPD whose short-circuit rating is below the prospective fault current can rupture; size Isccr ≥ Icc with the specified backup device.
- Treating the 120-240 V and 230/400 V bands with the same Uw — the withstand voltages differ, and so does the coordination margin.
Frequently asked questions
What is the difference between Uc, Up and Uw?
Uc (continuous operating voltage) is the voltage the SPD withstands permanently without conducting — set by the system and earthing. Up (voltage protection level) is the residual voltage the SPD lets through during a surge, from its datasheet. Uw is the rated impulse withstand voltage of the protected equipment. The whole sizing reduces to one inequality: the effective protection level Up + lead drop must stay below Uw.
How do I choose between Type 1, Type 2 and Type 3?
Position and lightning exposure decide it. At the service entrance with an LPS or an exposed overhead line, you need a Type 1 (tested with the 10/350 µs impulse current Iimp) to drain a direct lightning current. Without that exposure, the entrance and distribution boards use Type 2 (tested with the 8/20 µs In/Imax). Type 3 is fine protection installed next to sensitive equipment (≤ 10 m), always downstream of a Type 1/2 — never alone at the origin.
Why does the connection-lead length matter so much?
During a fast surge the inductance of the SPD leads produces an additional voltage of roughly 1 kV per metre. This drop adds directly to the SPD's Up, so the equipment actually sees Up + ΔU. Leads of just 1 m can push a 1.5 kV SPD up to 2.5 kV effective. That is why IEC/NBR require the connection (phase + PE) to be ≤ 0.5 m, ideally with a V-shaped connection.
How do I set Uc for an IT system?
In an IT system the first earth fault is not cleared, so the healthy phases rise toward the line-to-line voltage. The SPD between line and earth must therefore withstand √3·Uo continuously. For Uo = 230 V that is about 398 V, so a 420 or 440 V Uc is adopted — higher than the 275 V of a TN L-N SPD and the 385 V of a TT L-PE SPD.
What is Isccr and why provide the fault current?
Isccr is the SPD's short-circuit current rating — the prospective fault current it can interrupt safely together with its backup device (gG fuse or breaker). If the prospective fault current Icc at the installation point exceeds Isccr, the SPD can rupture during a power-frequency fault. Always size Isccr ≥ Icc, taking Icc from the short-circuit study.
What does the 20 % coordination margin mean?
Coordination only requires Up_effective ≤ Uw, but good practice keeps Up_effective ≤ 0.8·Uw — a 20 % headroom that absorbs SPD ageing, manufacturing tolerance and voltage oscillation at the equipment terminals. If you sit between 0.8·Uw and Uw the SPD still protects, but with little reserve; prefer a lower-Up SPD or shorter leads.
Glossary
- SPD
- Surge protective device: a component that limits transient overvoltages and diverts surge currents to earth, protecting downstream equipment.
- Uc
- Continuous operating voltage: the maximum RMS voltage the SPD can be permanently connected to without conducting or degrading.
- Up
- Voltage protection level: the residual voltage at the SPD terminals during the rated surge, from the datasheet; the lower it is, the better the protection.
- Uw
- Rated impulse withstand voltage of the protected equipment, defined by its overvoltage category in IEC 60364-4-44.
- Type (test class)
- SPD test class: Type 1 (10/350 µs Iimp, direct lightning, at the entrance), Type 2 (8/20 µs In/Imax, distribution boards), Type 3 (fine protection near the load).
- Iimp / In / Imax
- Surge currents: Iimp is the 10/350 µs impulse current of a Type 1 SPD; In is the 8/20 µs nominal discharge current; Imax the maximum 8/20 µs current a Type 2 withstands once.
- Isccr
- Short-circuit current rating: the prospective fault current the SPD withstands with its specified backup protection.