MCC sizing: drawers, incoming cubicle and busbar
Sizing an MCC (Motor Control Center) means choosing each drawer module from the starter type and power, selecting a motor breaker and contactor per load, summing the demand current for the main breaker and busbar, and packing it all into columns per IEC 61439.
When to use
Use it whenever you need to design or verify an MCC panel that feeds and protects a set of motors: pumping station, pump house, process plant, ventilation or conveyors. This method is the step that turns the load list (power, current, starter type) into a real physical layout — it sets each drawer's module size, the components in each compartment, the main breaker, the busbar cross-section and how many columns the assembly will occupy. It is also the tool to check whether an existing MCC can take a new load, or whether the busbar short-circuit rating matches the prospective fault current at the installation point.
What MCC sizing is
Sizing a Motor Control Center (MCC) is not just picking breakers: it is turning a load list — power, rated current, voltage and starter type for each motor — into a real physical layout of drawers, columns and busbar. The result is the switchgear assembly that will feed and protect the whole plant from a single incoming point, and it has to close on three fronts at once: protection (each motor with the right breaker and contactor), distribution (a busbar and main breaker that can carry the demand current) and space (each drawer fitting the usable column height, with a spare).
The method here follows the market reference — WEG CCM06 and Schneider Blokset — and the IEC 61439-1/2 standard governing low-voltage switchgear and controlgear assemblies. Every decision is deliberate and auditable: the drawer size comes from a power × starter rule, the components come from commercial series, and the column assembly follows a height-based packing.
The drawer: module by starter and power
The basic unit of the MCC is the drawer, a standardized (usually withdrawable) compartment that houses one motor’s starter. Its module — 1X, 2X, 3X or 4X — sets the height it occupies (200, 300, 400 and 600 mm respectively) and the room for components.
The size grows along two axes: the load power and the starter complexity.
- Feeder (no motor, distribution only): the criterion is current. In ≤ 63 A → 1X; ≤ 160 A → 2X; ≤ 400 A → 3X; above → 4X.
- DOL (direct-on-line): power sets the base. kW ≤ 7.5 → 1X; ≤ 30 → 2X; ≤ 75 → 3X; above → 4X.
- DOL reversing: adds one module to the DOL base (two contactors + interlock take more room), capped at 4X.
- Soft starter and VFD: have a 2X floor, because the electronic component does not fit in 1X; they rise to 3X/4X with power.
This rule reflects the physical reality of the catalog: a 30 kW reversing starter does not fit in the same bay as a 30 kW DOL, and a drive always demands more volume and more depth.
Components of each drawer
With the size set, the tool selects the switching and protection components per load, always rounding up to the first value of a commercial series:
- Motor circuit breaker (WEG MPW / Schneider GV): selected at 1.15 · In, to absorb the starting current and give the thermal trip range to set to the service factor. The series runs from 1.6 to 160 A.
- AC-3 contactor (WEG CWB / Schneider LC1): selected from the rated current In in utilization category AC-3 (squirrel-cage motors), from 9 to 630 A.
- Relay: thermal or intelligent protection relay (IR).
The composition changes with the starter: DOL takes motor breaker + contactor + relay; the reversing starter takes two contactors + interlock; the soft starter takes the electronic module + bypass contactor; and the VFD takes the drive in place of the switching contactor. The feeder takes only a distribution breaker sized by current.
The demand current and the incoming cubicle
No MCC is sized from the raw sum of rated currents — that would assume every load at full load at the same time. What sizes the assembly is the demand current:
I_dem = (Σ In_i · fd_i) · fs
where each load enters with its demand factor fd (how much it actually draws) and the whole assembly gets a diversity factor fs. It is this current that selects:
- the main breaker, in 3 poles, rounded up in the moulded-case series (16 to 1000 A);
- the main busbar cross-section, S = I_dem / J, with J between 1.5 and 2.5 A/mm² for copper in a ventilated assembly.
The incoming cubicle (the first column) concentrates the main breaker, the control transformer (mandatory), and optionally the power transformer (step-down), the heating transformer (if any motor has an anti-condensation heater), the 24 Vdc supply and the terminal blocks. The heights of these items must fit the usable column height; when they overflow, the method raises an “incoming column full” warning.
The short-circuit rating
Selecting rated currents is not enough — the MCC must survive a short circuit. The prospective fault current at the installation point, computed per IEC 60909 from the transformer and network impedance, sets the breaking capacity (Icu) of the breakers and the withstand (Icw) of the busbar.
The tool rounds the prospective Icc up in the commercial series (3 / 4.5 / 6 / 10 / 15 / 25 / 36 / 50 / 65 kA). This is where undersizing is most dangerous: a busbar with a kA below the prospective value may not contain a dead fault, and that is a safety failure, not just a performance one.
The column assembly
With drawers and incoming cubicle defined, the method packs everything into columns by a greedy height criterion:
- Column 0 is the incoming cubicle, with its own items.
- The load drawers (and the network drawer, if there are managed switches and remote I/O) are stacked into drawer columns: while it fits the usable height, the drawer goes in the current column; when it overflows, a new column is opened.
- The free space of the last column is filled with spare drawers (1X), and the method guarantees at least one required spare — opening a new column if needed. A spare is an expansion requirement of good practice and IEC 61439.
In the end, the total width is the sum of the column widths, the assembly height is the usable height plus base/roof (~300 mm), and the depth is 600 mm in the general case, rising to 800 mm when there is a VFD or soft starter (deep drawers).
Practical design considerations
- Always apply demand and diversity: sizing from the sum of rated currents inflates the main breaker, the busbar and the column count.
- Respect the 2X floor of electronic starters and the 800 mm depth — a drive does not fit in a DOL bay.
- Check the kA first: the short-circuit rating is the first safety verification; always round up.
- Reserve space: at least one free 1X drawer, ideally 20 % of the column, for the next load.
- Count the incoming cubicle in the usable height: the control transformer, supply and terminal blocks consume real height and cannot be forgotten.
Following this chain — drawer size by starter, components by commercial series, demand current, main breaker and busbar, short-circuit rating and column packing — yields an MCC that is numerically rigorous and meets IEC 61439 on site.
Formulas and fundamentals
I_brk = next(1.15 · In, breaker_series) The motor breaker is selected above the load's rated current to absorb starting/inrush and to allow the thermal trip to be set to the service factor. In is the motor rated current [A]; the 1.15 factor gives the margin; next() rounds up to the first commercial value in the series (1.6 / 2.5 / 4 / 6.3 / 10 / 16 / 25 / 32 / 40 / 50 / 63 / 80 / 100 / 125 / 160 A).
I_cont = next(In, contactor_series) The switching contactor is selected in utilization category AC-3 (squirrel-cage motors) from the rated current In [A], rounding up to the first commercial value (9 / 12 / 18 / 25 / 32 / 40 / 50 / 65 / 80 / 95 / 115 / 150 / 185 / 225 / 265 / 300 / 400 / 500 / 630 A). Reversing starters take two contactors; soft starters add a bypass contactor.
I_dem = ( Σ In_i · fd_i ) · fs The current the assembly actually draws. For each load i, In_i is the rated current [A] and fd_i its individual demand factor [dimensionless]; the sum is multiplied by the diversity factor fs [dimensionless] of the whole MCC. It is this current, not the sum of the rated values, that sizes the main breaker and the busbar.
I_main = next(I_dem, main_series) The MCC main breaker is selected above the demand current I_dem [A], from the moulded-case/air series (16 / 25 / 32 / 40 / 50 / 63 / 80 / 100 / 125 / 160 / 200 / 250 / 320 / 400 / 630 / 800 / 1000 A), in 3 poles. The breaking capacity (kA) is a separate matter, set by the prospective fault current.
S = I_dem / J Cross-sectional area of the main copper busbar. I_dem is the demand current [A] and J the admissible current density [A/mm²], typically 1.5 to 2.5 A/mm² for copper bars in a ventilated assembly. S comes out in mm² and must be rounded up to the next commercial bar.
kA_rec = next(Icc_prospective, kA_series) The short-circuit rating of the busbar and breakers must meet or exceed the prospective fault current at the installation point. Icc_prospective [kA] is rounded up in the commercial series (3 / 4.5 / 6 / 10 / 15 / 25 / 36 / 50 / 65 kA). Undersizing here is the most dangerous mistake in the design.
Standards & methods
- IEC 61439-1 — Low-voltage switchgear and controlgear assemblies: general rules
- IEC 61439-2 — Power switchgear and controlgear assemblies (PSC), applicable to MCC
- IEC 60947-4-1 — Contactors and motor starters (utilization category AC-3)
- ABNT NBR 5410 — Low-voltage electrical installations (motor protection §6.5)
- ABNT NBR 14039 — Medium-voltage electrical installations (incoming/protection)
- IEC 60909 — Short-circuit current calculation (prospective Icc)
Typical reference values
| Quantity | Typical range | Note |
|---|---|---|
| Copper busbar current density | 1.5 to 2.5 A/mm² | Ventilated assembly; lower values for confined bars or severe continuous duty. |
| Usable column height | 1800 to 2000 mm | A 2200 mm floor-standing panel less base and roof (~300 mm). |
| Standard column width | 600 to 800 mm | WEG CCM06 and Schneider Blokset work in modules; 600 mm is the usual step. |
| Assembly depth | 600 mm (DOL) to 800 mm (VFD/soft) | Drives and soft starters need deeper drawers for heat dissipation. |
| Per-motor demand factor | 0.7 to 1.0 | Loads that do not run simultaneously lower the factor; duty/standby pumps, for example. |
| Motor-breaker margin | 1.1 to 1.25 · In | Ensures the thermal trip can be set to the service factor without tripping on start. |
Worked example
Three-motor MCC at 380 V (pump, fan and conveyor)
Inputs
- Motor 1 — pump (DOL)
- 30 kW; In = 57 A
- Motor 2 — fan (DOL)
- 7.5 kW; In = 15 A
- Motor 3 — conveyor (VFD)
- 45 kW; In = 84 A
- Demand / diversity factors
- fd = 0.8; fs = 0.9 dimensionless
- Prospective fault current
- Icc = 18 kA
- Busbar current density
- J = 2.0 A/mm²
- Usable column height
- 1800 mm
Results
- Pump drawer 30 kW DOL
- 2X; brk 80; cont 65 mm/A
- Fan drawer 7.5 kW DOL
- 1X; brk 25; cont 18 mm/A
- Conveyor drawer 45 kW VFD
- 3X; brk 100; cont 95 mm/A
- Total demand current
- I_dem ≈ 112.3 A
- Main breaker (3 poles)
- 125 A
- Busbar cross-section
- S ≈ 56.2 mm²
- Recommended kA / depth
- 25 kA; 800 kA/mm
The 30 kW DOL pump falls in the kW ≤ 30 band → 2X drawer (300 mm); its motor breaker is next(1.15·57 = 65.6) = 80 A and the AC-3 contactor is next(57) = 65 A. The 7.5 kW fan is 1X (200 mm) with a 25 A breaker and an 18 A contactor. The 45 kW VFD conveyor, although below 75 kW, takes 3X (400 mm) and pushes the panel depth to 800 mm. The demand current is (57+15+84)·0.8·0.9 ≈ 112.3 A, which sets the main breaker at 125 A/3P and the busbar at 112.3/2.0 ≈ 56.2 mm² (round up to the next commercial bar). The 18 kA prospective fault leads to a recommended 25 kA rating. The three drawers (900 mm) plus the incoming cubicle (main 250 + control transformer 150 + 24 Vdc supply 120 + terminal blocks 150 = 670 mm) fit comfortably in 1800 mm usable columns, leaving room for the required spare drawer.
Common mistakes
- Summing rated currents without applying demand and diversity factors — oversizes the main breaker, the busbar and the panel width.
- Selecting the motor breaker exactly at In: it trips on start or leaves no margin to set the thermal to the service factor.
- Forgetting the busbar short-circuit rating (kA): an MCC with Icc below the prospective fault at the point cannot withstand the fault and is a serious safety failure.
- Sizing a VFD or soft-starter drawer the same module as a DOL of equal power — the electronic starter needs more space and a deeper panel.
- Not allowing a spare drawer: IEC 61439 and good practice require expansion space; without a spare, any new load forces a new column.
- Ignoring the incoming cubicle (control transformer, 24 Vdc supply, terminal blocks) when counting usable height — the incoming column fills up and pushes load further along.
Frequently asked questions
How is the drawer module (1X to 4X) decided?
The size grows with power and with starter complexity. For feeders, current rules (≤63 A → 1X, ≤160 A → 2X, ≤400 A → 3X, above → 4X). For DOL motors, power sets the base (≤7.5 kW → 1X, ≤30 kW → 2X, ≤75 kW → 3X, above → 4X); a reversing starter adds one module, and soft starters and VFDs have a 2X floor because of the electronic component. Each module has a standard height (1X = 200 mm, 2X = 300, 3X = 400, 4X = 600).
Why is the motor breaker larger than the rated current?
Because the starting current of an induction motor reaches 6–8 times the rated value for a few seconds, and the breaker must not trip on that transient. It is selected above the rated value (here, 1.15·In rounded up to the commercial series) so the thermal overload relay has range to set to the service factor without tripping on start. Selecting exactly at In undersizes the protection.
What is the difference between the sum of rated currents and the demand current?
Summing the rated currents assumes all loads run at the same time at full load — almost never true. The demand current applies a demand factor per load (how much each actually draws) and a diversity factor to the assembly (how many run together). It is the demand, always lower than the raw sum, that sizes the main breaker and the busbar.
How do I choose the MCC short-circuit rating (kA)?
From the prospective short-circuit current at the installation point, computed per IEC 60909 from the transformer and network impedance. The busbar and breakers must have a breaking/withstand capacity (Icu/Icw) equal to or greater than that current. The tool rounds the Icc up in the commercial series (3 to 65 kA); never round down.
What goes in the incoming cubicle?
The incoming cubicle concentrates the main breaker, the control transformer (mandatory, for the control voltage), optionally the power transformer (step-down), the heating transformer (if any motor has an anti-condensation heater), the 24 Vdc supply and the terminal blocks. The heights of these items must fit the usable height of the incoming column, otherwise the tool warns that the column is full.
Why reserve an empty drawer?
IEC 61439 and good design practice require expansion capacity. The tool fills the free space of the last column with spare drawers (1X) and guarantees at least one spare, opening a new column if needed. Without a spare, any motor added later forces a new cubicle and a busbar rework.
Glossary
- MCC
- Motor Control Center: a low-voltage switchgear assembly that groups, in drawers/cubicles, the protection and control of several motors from a common busbar.
- Drawer
- A standardized and (usually) withdrawable MCC compartment that houses one motor's starter. The 1X to 4X module sets its height and component space.
- Motor circuit breaker
- A breaker with magnetic (short-circuit) and adjustable thermal (overload) protection dedicated to one motor, selected above the rated current.
- AC-3 contactor
- An electromechanical switching device in utilization category AC-3 (squirrel-cage motors) that switches the motor on and off under load.
- Busbar
- The set of copper (or aluminium) bars distributing current from the main breaker to the drawers; its cross-section follows from the demand current and the admissible density.
- Demand current
- The current actually drawn by the assembly, obtained by applying demand and diversity factors to the sum of rated currents.
- Prospective Icc
- The short-circuit current expected at the installation point (IEC 60909); it sets the breaking and withstand capacity required of the busbar and breakers.
- VFD / soft starter
- Electronic starters — variable frequency drive (VFD) and soft starter — that reduce starting current but take a larger drawer and a deeper panel.