Electrical

NBR 5410 ampacity tables (current-carrying capacity)

Current-carrying capacity (ampacity) of low-voltage cables per ABNT NBR 5410, for copper and aluminum conductors, PVC 70 °C and EPR/XLPE 90 °C insulation, installation methods A1 to F — the tables the LOGOS cable-sizing engine applies before correction factors.

What these tables give

Ampacity (Iz) is the continuous current a cable can carry without its conductor exceeding the insulation temperature limit — 70 °C for PVC, 90 °C for EPR/XLPE. The values below reproduce the NBR 5410 series (Tables 36 to 39, aligned with IEC 60364-5-52) for 3 loaded conductors, ambient 30 °C in air and 20 °C in the ground, sections 2.5 to 630 mm².

The installation methods (columns A1 to F)

  • A1 — insulated conductors in conduit inside a thermally insulating wall;
  • A2 — multicore cable in conduit inside a thermally insulating wall;
  • B1 — insulated conductors in conduit on a wall (apparent);
  • B2 — multicore cable in conduit on a wall;
  • C — cables on a wall or non-perforated tray;
  • D — cables in buried ducts;
  • E — multicore cable on perforated tray or ladder;
  • F — single-core cables in trefoil on perforated tray or ladder.

The same section can differ by 40% or more between methods: a 95 mm² XLPE copper cable carries 216 A embedded (A1) and 328 A in trefoil on a ladder (F). Getting the method right is worth more than one section step.

What still needs to be applied on top

The table Iz assumes the reference ambient and a single circuit. Real capacity is:

Iz' = Iz × Ft × Fa (× Fs × Fp for buried lines)

where Ft corrects for ambient temperature, Fa for grouping of circuits, Fs for soil thermal resistivity and Fp for burial depth. All factor tables are on the NBR 5410 correction factors page of this reference section. Cable sizing must also check voltage drop and short-circuit withstand independently — the LOGOS cable engine runs all criteria at once.

Copper · PVC 70 °C (NBR 5410 Tables 36/38)

Cross-section (mm²)A1A2B1B2CDEF
2.51817.5212024242524
42423282732313433
63129363441394343
104239504657526060
165652686276678082
25736889809686101110
35898311099119103126137
5010899134118144122153167
70136125171149184151196216
95164150207179223179238264
120188172239206259203276308
150216196275236299230319356
185245223314268341258364409
240286261370313403297430485
300328298426358464336497561
400390355510425557394597656
500447406587486642445689749
630514467678559743506798855

Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.

Copper · EPR/XLPE 90 °C (NBR 5410 Tables 37/39)

Cross-section (mm²)A1A2B1B2CDEF
2.52322282630293229
43130373540374240
64038484452465453
105451666071617574
16736888809679100101
259589117105119101127135
35117109144128147122158169
50141130175154179144192207
70179164222194229178246268
95216197269233278211298328
120249227312268322240346383
150285259358307371271399444
185324295408348424304456510
240380346481407500351538607
300435396553465576396621703
400519472661552692464745823
500595541760631797525859946
6306856238797259235969951088

Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.

Aluminum · PVC 70 °C (from 16 mm²)

Cross-section (mm²)A1A2B1B2CDEF
164341534859526162
255753706273667884
3570658677908096105
5084781049211094117128
7010798133116140117150166
95129118161139170138183203
120149135186160197157212237
150170155214183227178245274
185194176245208259200280315
240227207288243305230330375
300261237331278351260381434
400311283397331422305458526
500356324456378486345528610
630410373527435562391613711

Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.

Aluminum · EPR/XLPE 90 °C (from 16 mm²)

Cross-section (mm²)A1A2B1B2CDEF
165855716476617776
2576719384907897103
35948711610311294120129
50113104140124136112146159
70142131179156174138187206
95171157217188211164227253
120197180251216245186263296
150226206289248283210304343
185256233330281323236347395
240300273389329382272409471
300344313447377440308471547
400409372536448529361566663
500468426617513610408652770
630538490714590707464755899

Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.

Standards & methods

  • ABNT NBR 5410 (Tables 36–39)
  • IEC 60364-5-52
  • NBR NM 280 (conductors)

Frequently asked questions

Which installation method should I use for conduit embedded in a wall?

Insulated conductors in conduit in a thermally insulating wall is A1 (multicore cable: A2). Conduit on a wall surface (apparent) is B1/B2 — noticeably higher ampacity, because the wall stops insulating and starts dissipating.

Why does XLPE/EPR carry more current than PVC in the same section?

Because the insulation withstands a higher continuous conductor temperature: 90 °C vs 70 °C. The higher allowed temperature rise above the same 30 °C ambient means more dissipated power, hence more current — typically 20–25% more for the same section and method.

Are these values final for sizing?

No — they are the table base Iz. The real capacity is Iz corrected by the temperature factor (ambient ≠ 30 °C air / 20 °C ground) and the grouping factor (more than one loaded circuit together), plus soil resistivity and depth for buried lines. Sizing must also independently satisfy voltage drop and short-circuit withstand.

When does the neutral count as a loaded conductor?

In three-phase circuits with third-harmonic content above 33% (typical of LED lighting and electronic loads), the neutral carries near-phase current and the circuit must be treated as 4 loaded conductors — NBR 5410 applies a 0.86 factor on the 3-conductor table.

Can I use aluminum conductors in any section?

NBR 5410 only admits aluminum from 16 mm² up (and with additional restrictions in commercial installations, from 50 mm²). That is why the aluminum tables here start at 16 mm².

Use these values in a calculator

More reference tables