NBR 5410 ampacity tables (current-carrying capacity)
Current-carrying capacity (ampacity) of low-voltage cables per ABNT NBR 5410, for copper and aluminum conductors, PVC 70 °C and EPR/XLPE 90 °C insulation, installation methods A1 to F — the tables the LOGOS cable-sizing engine applies before correction factors.
What these tables give
Ampacity (Iz) is the continuous current a cable can carry without its conductor exceeding the insulation temperature limit — 70 °C for PVC, 90 °C for EPR/XLPE. The values below reproduce the NBR 5410 series (Tables 36 to 39, aligned with IEC 60364-5-52) for 3 loaded conductors, ambient 30 °C in air and 20 °C in the ground, sections 2.5 to 630 mm².
The installation methods (columns A1 to F)
- A1 — insulated conductors in conduit inside a thermally insulating wall;
- A2 — multicore cable in conduit inside a thermally insulating wall;
- B1 — insulated conductors in conduit on a wall (apparent);
- B2 — multicore cable in conduit on a wall;
- C — cables on a wall or non-perforated tray;
- D — cables in buried ducts;
- E — multicore cable on perforated tray or ladder;
- F — single-core cables in trefoil on perforated tray or ladder.
The same section can differ by 40% or more between methods: a 95 mm² XLPE copper cable carries 216 A embedded (A1) and 328 A in trefoil on a ladder (F). Getting the method right is worth more than one section step.
What still needs to be applied on top
The table Iz assumes the reference ambient and a single circuit. Real capacity is:
Iz' = Iz × Ft × Fa (× Fs × Fp for buried lines)
where Ft corrects for ambient temperature, Fa for grouping of circuits, Fs for soil thermal resistivity and Fp for burial depth. All factor tables are on the NBR 5410 correction factors page of this reference section. Cable sizing must also check voltage drop and short-circuit withstand independently — the LOGOS cable engine runs all criteria at once.
Copper · PVC 70 °C (NBR 5410 Tables 36/38)
| Cross-section (mm²) | A1 | A2 | B1 | B2 | C | D | E | F |
|---|---|---|---|---|---|---|---|---|
| 2.5 | 18 | 17.5 | 21 | 20 | 24 | 24 | 25 | 24 |
| 4 | 24 | 23 | 28 | 27 | 32 | 31 | 34 | 33 |
| 6 | 31 | 29 | 36 | 34 | 41 | 39 | 43 | 43 |
| 10 | 42 | 39 | 50 | 46 | 57 | 52 | 60 | 60 |
| 16 | 56 | 52 | 68 | 62 | 76 | 67 | 80 | 82 |
| 25 | 73 | 68 | 89 | 80 | 96 | 86 | 101 | 110 |
| 35 | 89 | 83 | 110 | 99 | 119 | 103 | 126 | 137 |
| 50 | 108 | 99 | 134 | 118 | 144 | 122 | 153 | 167 |
| 70 | 136 | 125 | 171 | 149 | 184 | 151 | 196 | 216 |
| 95 | 164 | 150 | 207 | 179 | 223 | 179 | 238 | 264 |
| 120 | 188 | 172 | 239 | 206 | 259 | 203 | 276 | 308 |
| 150 | 216 | 196 | 275 | 236 | 299 | 230 | 319 | 356 |
| 185 | 245 | 223 | 314 | 268 | 341 | 258 | 364 | 409 |
| 240 | 286 | 261 | 370 | 313 | 403 | 297 | 430 | 485 |
| 300 | 328 | 298 | 426 | 358 | 464 | 336 | 497 | 561 |
| 400 | 390 | 355 | 510 | 425 | 557 | 394 | 597 | 656 |
| 500 | 447 | 406 | 587 | 486 | 642 | 445 | 689 | 749 |
| 630 | 514 | 467 | 678 | 559 | 743 | 506 | 798 | 855 |
Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.
Copper · EPR/XLPE 90 °C (NBR 5410 Tables 37/39)
| Cross-section (mm²) | A1 | A2 | B1 | B2 | C | D | E | F |
|---|---|---|---|---|---|---|---|---|
| 2.5 | 23 | 22 | 28 | 26 | 30 | 29 | 32 | 29 |
| 4 | 31 | 30 | 37 | 35 | 40 | 37 | 42 | 40 |
| 6 | 40 | 38 | 48 | 44 | 52 | 46 | 54 | 53 |
| 10 | 54 | 51 | 66 | 60 | 71 | 61 | 75 | 74 |
| 16 | 73 | 68 | 88 | 80 | 96 | 79 | 100 | 101 |
| 25 | 95 | 89 | 117 | 105 | 119 | 101 | 127 | 135 |
| 35 | 117 | 109 | 144 | 128 | 147 | 122 | 158 | 169 |
| 50 | 141 | 130 | 175 | 154 | 179 | 144 | 192 | 207 |
| 70 | 179 | 164 | 222 | 194 | 229 | 178 | 246 | 268 |
| 95 | 216 | 197 | 269 | 233 | 278 | 211 | 298 | 328 |
| 120 | 249 | 227 | 312 | 268 | 322 | 240 | 346 | 383 |
| 150 | 285 | 259 | 358 | 307 | 371 | 271 | 399 | 444 |
| 185 | 324 | 295 | 408 | 348 | 424 | 304 | 456 | 510 |
| 240 | 380 | 346 | 481 | 407 | 500 | 351 | 538 | 607 |
| 300 | 435 | 396 | 553 | 465 | 576 | 396 | 621 | 703 |
| 400 | 519 | 472 | 661 | 552 | 692 | 464 | 745 | 823 |
| 500 | 595 | 541 | 760 | 631 | 797 | 525 | 859 | 946 |
| 630 | 685 | 623 | 879 | 725 | 923 | 596 | 995 | 1088 |
Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.
Aluminum · PVC 70 °C (from 16 mm²)
| Cross-section (mm²) | A1 | A2 | B1 | B2 | C | D | E | F |
|---|---|---|---|---|---|---|---|---|
| 16 | 43 | 41 | 53 | 48 | 59 | 52 | 61 | 62 |
| 25 | 57 | 53 | 70 | 62 | 73 | 66 | 78 | 84 |
| 35 | 70 | 65 | 86 | 77 | 90 | 80 | 96 | 105 |
| 50 | 84 | 78 | 104 | 92 | 110 | 94 | 117 | 128 |
| 70 | 107 | 98 | 133 | 116 | 140 | 117 | 150 | 166 |
| 95 | 129 | 118 | 161 | 139 | 170 | 138 | 183 | 203 |
| 120 | 149 | 135 | 186 | 160 | 197 | 157 | 212 | 237 |
| 150 | 170 | 155 | 214 | 183 | 227 | 178 | 245 | 274 |
| 185 | 194 | 176 | 245 | 208 | 259 | 200 | 280 | 315 |
| 240 | 227 | 207 | 288 | 243 | 305 | 230 | 330 | 375 |
| 300 | 261 | 237 | 331 | 278 | 351 | 260 | 381 | 434 |
| 400 | 311 | 283 | 397 | 331 | 422 | 305 | 458 | 526 |
| 500 | 356 | 324 | 456 | 378 | 486 | 345 | 528 | 610 |
| 630 | 410 | 373 | 527 | 435 | 562 | 391 | 613 | 711 |
Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.
Aluminum · EPR/XLPE 90 °C (from 16 mm²)
| Cross-section (mm²) | A1 | A2 | B1 | B2 | C | D | E | F |
|---|---|---|---|---|---|---|---|---|
| 16 | 58 | 55 | 71 | 64 | 76 | 61 | 77 | 76 |
| 25 | 76 | 71 | 93 | 84 | 90 | 78 | 97 | 103 |
| 35 | 94 | 87 | 116 | 103 | 112 | 94 | 120 | 129 |
| 50 | 113 | 104 | 140 | 124 | 136 | 112 | 146 | 159 |
| 70 | 142 | 131 | 179 | 156 | 174 | 138 | 187 | 206 |
| 95 | 171 | 157 | 217 | 188 | 211 | 164 | 227 | 253 |
| 120 | 197 | 180 | 251 | 216 | 245 | 186 | 263 | 296 |
| 150 | 226 | 206 | 289 | 248 | 283 | 210 | 304 | 343 |
| 185 | 256 | 233 | 330 | 281 | 323 | 236 | 347 | 395 |
| 240 | 300 | 273 | 389 | 329 | 382 | 272 | 409 | 471 |
| 300 | 344 | 313 | 447 | 377 | 440 | 308 | 471 | 547 |
| 400 | 409 | 372 | 536 | 448 | 529 | 361 | 566 | 663 |
| 500 | 468 | 426 | 617 | 513 | 610 | 408 | 652 | 770 |
| 630 | 538 | 490 | 714 | 590 | 707 | 464 | 755 | 899 |
Current in amperes, 3 loaded conductors, ambient 30 °C (air) / 20 °C (ground). Same table the LOGOS cable sizing engine uses.
Standards & methods
- ABNT NBR 5410 (Tables 36–39)
- IEC 60364-5-52
- NBR NM 280 (conductors)
Frequently asked questions
Which installation method should I use for conduit embedded in a wall?
Insulated conductors in conduit in a thermally insulating wall is A1 (multicore cable: A2). Conduit on a wall surface (apparent) is B1/B2 — noticeably higher ampacity, because the wall stops insulating and starts dissipating.
Why does XLPE/EPR carry more current than PVC in the same section?
Because the insulation withstands a higher continuous conductor temperature: 90 °C vs 70 °C. The higher allowed temperature rise above the same 30 °C ambient means more dissipated power, hence more current — typically 20–25% more for the same section and method.
Are these values final for sizing?
No — they are the table base Iz. The real capacity is Iz corrected by the temperature factor (ambient ≠ 30 °C air / 20 °C ground) and the grouping factor (more than one loaded circuit together), plus soil resistivity and depth for buried lines. Sizing must also independently satisfy voltage drop and short-circuit withstand.
When does the neutral count as a loaded conductor?
In three-phase circuits with third-harmonic content above 33% (typical of LED lighting and electronic loads), the neutral carries near-phase current and the circuit must be treated as 4 loaded conductors — NBR 5410 applies a 0.86 factor on the 3-conductor table.
Can I use aluminum conductors in any section?
NBR 5410 only admits aluminum from 16 mm² up (and with additional restrictions in commercial installations, from 50 mm²). That is why the aluminum tables here start at 16 mm².