Surge arrester sizing: Uc, Ur, TOV capability and NBI protective margin
Sizing a metal-oxide (ZnO) surge arrester means setting its continuous operating voltage Uc above the system phase-to-ground voltage, choosing a rated voltage Ur that survives the temporary overvoltage (TOV), and confirming that the residual voltage Up leaves an adequate protective margin against the equipment BIL.
When to use
Use it whenever you need to specify or verify a metal-oxide surge arrester protecting a transformer, busbar, cable termination or rotating machine against switching and lightning surges. It is the closing step of insulation coordination: you already know the maximum system voltage (Um) and the insulation level (BIL/NBI) of the equipment, and you must pick an arrester whose continuous voltage tolerates normal operation, whose rated voltage rides through the temporary overvoltage during a ground fault, and whose protective level still clamps the surge well below the BIL. It is also the tool to audit existing arresters that fail prematurely — almost always because Uc was set too low for the actual TOV or harmonic content.
What surge arrester sizing is
A surge arrester is the last line of defence of insulation coordination. It is a voltage-dependent resistor — a stack of metal-oxide (zinc-oxide, ZnO) blocks — that behaves like an open circuit at normal voltage and like a near short circuit when an overvoltage appears, diverting the surge current to ground and clamping the voltage across the protected equipment.
Sizing it is a balancing act between two opposing requirements. On one hand, the arrester must tolerate the highest voltage that normal operation and temporary faults impose, or it ages and fails. On the other hand, it must clamp lightning and switching surges to a residual voltage low enough to protect the equipment insulation. The continuous voltage Uc and rated voltage Ur cover the first requirement; the residual voltage Up and its margin against the BIL cover the second.
The method below follows IEC 60099-4 / NBR 16050 and the application guidance of IEC 60099-5 and IEEE C62.22.
Step 1 — the voltage the arrester sees continuously
The arrester is connected phase-to-ground, so the steady-state voltage across it is the maximum phase-to-ground system voltage:
U_L-N,max = (Um/√3)·(1 + reg)
Here Um is the maximum system voltage (for a 13.8 kV nominal network, Um = 15 kV) and reg is the steady-state overvoltage from regulation or light-load conditions. The continuous operating voltage Uc must sit above this value with margin for harmonics and metering tolerance:
Uc_req = 1.05 · U_L-N,max
The 1.05 factor is not arbitrary: third-harmonic content and instrument tolerance routinely add a few percent to the fundamental. An arrester whose Uc only just equals the nominal phase-to-ground voltage will draw excessive resistive leakage current, heat up, and drift up the ageing curve. On isolated or resonant-grounded systems a ground fault can persist indefinitely, raising the sound phases toward line-to-line voltage; in that sustained-fault case the calculator references Uc to Um directly rather than to Um/√3.
Step 2 — from Uc to the rated voltage Ur
For standard metal-oxide arresters the continuous voltage is about 80% of the rated voltage, so the first lower bound on Ur is:
Ur(Uc) = Uc_req / 0.8 ≈ 1.25 · Uc_req
Ur is the 10-second power-frequency reference voltage that names the arrester (a “12 kV arrester”). But Uc is not the only constraint — the temporary overvoltage gives a second, independent one.
Step 3 — the temporary overvoltage (TOV) criterion
When a single phase faults to ground, the two healthy phases rise. The power-frequency overvoltage on the sound phases is:
Utov = k · U_L-N,max
where k is the earth-fault factor: about 1.3–1.4 on a solidly grounded system, climbing toward √3 ≈ 1.73 on an isolated or high-impedance system. The arrester can absorb this overvoltage only for a limited time before thermal runaway, and its TOV capability Tt (expressed per unit of Ur) decreases with duration — roughly 1.20 for sub-second events, 1.15 at 1 s, 1.10 at 10 s, and around 1.04 for very long faults. The rated voltage required by the TOV is therefore:
Ur(TOV) = Utov / Tt
The arrester must satisfy both criteria, so the design Ur is the next standard rating at or above the larger of the two:
Ur = next_standard(max(Ur(Uc), Ur(TOV)))
Once Ur is fixed at a catalog value, the actual arrester continuous voltage is recovered as Uc = 0.8·Ur, which must still cover Uc_req.
Step 4 — residual voltage and protective margin
The whole point of the arrester is the residual (protective) voltage Up — the voltage that remains across it while it discharges the nominal current In (an 8/20 µs impulse of 5, 10 or 20 kA depending on class). Up comes from the datasheet ratio Up/Ur, typically between 3.0 and 3.5:
Up = (Up/Ur) · Ur
This Up is compared against the equipment basic lightning impulse insulation level (BIL/NBI) to get the protective margin:
margin = (BIL/Up − 1) · 100 ≥ 20 %
A margin of at least 20% is the usual acceptance threshold. Cables, gas-insulated switchgear and rotating machines deserve more, because their insulation does not self-restore. Note that the effective margin at the equipment terminals is eroded by the inductance of the leads connecting the arrester — keep those leads short and direct.
Step 5 — the short-circuit (pressure-relief) rating
Finally, the arrester must fail safely. Its rated short-circuit / pressure-relief current Is must equal or exceed the prospective fault current Ik″ at the installation point:
Is ≥ Ik″
If the arrester is ever overstressed to failure, it should vent the fault current in a controlled way rather than rupture its housing violently. The calculator rounds Ik″ up to the next standard Is rating (5, 10, 16, 20, 31.5, 40 kA…).
How to read the result
The selection is consistent when all of the following hold:
- The adopted Ur is a standard value at or above both Ur(Uc) and Ur(TOV).
- The arrester Uc = 0.8·Ur still covers the required Uc.
- The protective margin (BIL vs Up) meets or exceeds the target (≥ 20%).
- The nominal discharge current In matches the application class.
- Is ≥ Ik″ so the failure mode is safe.
If the protective margin is negative or below target, the arrester clamps too high for that insulation level — you need a lower Up, which usually means a lower Ur (only possible if the TOV/Uc criteria allow) or a higher-energy arrester class with a better Up/Ur ratio. If instead the TOV criterion dominates and forces a high Ur, the protective margin shrinks; this is the classic tension on weakly grounded systems, where a higher Ur is unavoidable and the equipment BIL may have to be reconsidered.
Practical design considerations
- Always check both criteria. Uc protects against continuous duty and harmonics; TOV protects against the ground-fault overvoltage. The required Ur is the worse of the two — never just one.
- Match the earth-fault factor to the real grounding. Defaulting to k = 1.4 on an isolated system badly undersizes the arrester.
- Use the TOV capability for the actual clearing time. A relay that takes several seconds to clear demands a higher Ur than a fast one.
- Keep arrester leads short. Lead inductance adds to Up at the equipment terminals and quietly eats into the protective margin.
- Verify Is against the site fault level. A correct Up is worthless if the arrester cannot fail safely.
Following this chain — U_L-N,max, Uc, the two Ur criteria, the standard Ur, Up and its margin against the BIL, and finally Is — yields an arrester selection that is coordinated with the equipment insulation and robust against both continuous duty and temporary faults.
Formulas and fundamentals
U_L-N,max = (Um/√3)·(1 + reg) Highest steady-state voltage the arrester sees between phase and ground. Um is the maximum system voltage [kV], the √3 converts line to phase voltage, and reg is the steady-state overvoltage (regulation/load-rejection) as a fraction. On an isolated or resonant-grounded system with a sustained fault, the arrester effectively sees the line-to-line voltage and Um is used directly.
Uc_req = 1.05 · U_L-N,max (sustained fault: 1.05 · Um · (1 + reg)) Minimum continuous voltage the arrester must withstand indefinitely. The 1.05 factor covers harmonics and metering tolerance. On a sustained ground fault (isolated/resonant grounding), the healthy phases rise toward line-to-line voltage, so Uc is referenced to Um.
Ur(Uc) = Uc_req / 0.8 (i.e. Ur ≈ 1.25 · Uc) For standard MO arresters the continuous voltage is about 0.8 of the rated voltage, so Ur must be at least Uc/0.8. Ur is the 10-second power-frequency reference voltage of the arrester.
Utov = k · U_L-N,max ; Ur(TOV) = Utov / Tt Utov is the power-frequency overvoltage on the sound phases during a ground fault, where k is the earth-fault factor (≈1.4 solidly grounded, up to √3 isolated). Tt is the arrester TOV capability (per unit of Ur) for the fault duration, read from the manufacturer 10 s / longer-duration curve. Ur must satisfy both Ur(Uc) and Ur(TOV).
Up = (Up/Ur) · Ur ; margin = (BIL/Up − 1)·100 ≥ target Up is the residual (protective) voltage at the nominal discharge current In, obtained from the datasheet ratio Up/Ur (typically 3.0–3.5). The protective margin against the equipment lightning impulse withstand (BIL/NBI) should be at least 20%, i.e. Up should be well below the BIL.
Is ≥ Ik″ The arrester rated short-circuit / pressure-relief current Is must equal or exceed the prospective fault current Ik″ available at the installation point, so the arrester fails safely (no violent rupture) if it is overstressed.
Standards & methods
- IEC 60099-4 — Surge arresters – Part 4: Metal-oxide surge arresters without gaps for a.c. systems
- IEC 60099-5 — Surge arresters – Part 5: Selection and application recommendations
- ABNT NBR 16050 — Surge arresters of metal oxide without gaps for a.c. systems – Selection and application
- IEC 60071-1 / 60071-2 — Insulation co-ordination: definitions and application guide
- IEEE C62.11 / C62.22 — Metal-oxide surge arresters and application guide for a.c. systems
Typical reference values
| Quantity | Typical range | Note |
|---|---|---|
| Uc / Ur ratio (MCOV) | ≈ 0.80 | Standard MO arresters: continuous voltage is about 80% of the rated voltage. |
| Earth-fault factor k | 1.3–1.4 (solidly grounded) · up to √3 (isolated) | Solidly grounded systems keep k ≤ 1.4; ungrounded/resonant systems approach 1.73. |
| Up / Ur ratio at In | ≈ 3.0 to 3.5 | Switching-impulse and lightning-impulse residual ratios from the datasheet. |
| Protective margin against BIL | ≥ 20 % | IEC/IEEE practice; larger margins for cables and rotating machines. |
| Nominal discharge current In | 5 kA (distribution) · 10 kA (≤245 kV) · 20 kA (EHV) | Class defined by IEC 60099-4 line discharge / energy class. |
| TOV capability Tt (10 s) | ≈ 1.10–1.15 p.u. of Ur | Falls toward ~1.04 for very long durations; rises toward ~1.20 for sub-second faults. |
Worked example
Arrester for a 13.8 kV (Um = 15 kV) solidly grounded distribution transformer
Inputs
- Maximum system voltage Um
- 15 kV
- Steady-state regulation
- 5 %
- Earth-fault factor k
- 1.4 —
- TOV duration
- 3 s
- Up/Ur ratio (datasheet)
- 3.3 —
- Equipment BIL (NBI)
- 110 kV
- Prospective fault current Ik″
- 12.5 kA
Results
- U_L-N,max
- 9.1 kV
- Required Uc
- 9.5 kV
- Ur from Uc / from TOV
- 11.9 / 11.3 kV
- Adopted Ur (standard)
- 12 kV
- Residual voltage Up at In
- 39.6 kV
- Protective margin vs BIL
- 178 %
- Required Is (≥ Ik″)
- 16 kA
The arrester sees U_L-N,max = (15/√3)·1.05 ≈ 9.1 kV, so Uc must be at least 1.05·9.1 ≈ 9.5 kV, giving Ur(Uc) = 9.5/0.8 ≈ 11.9 kV. The TOV is k·U_L-N,max = 1.4·9.1 ≈ 12.7 kV; at 3 s the capability Tt ≈ 1.13, so Ur(TOV) = 12.7/1.13 ≈ 11.3 kV. The governing value is max(11.9, 11.3) = 11.9 kV, rounded up to the standard Ur = 12 kV (then Uc of the chosen arrester = 0.8·12 = 9.6 kV ≥ 9.5 kV, OK). With Up/Ur = 3.3 the residual is Up = 3.3·12 ≈ 39.6 kV, leaving a margin of (110/39.6 − 1)·100 ≈ 178% — far above the 20% target. A 10 kA In, 16 kA short-circuit-rated arrester completes the selection.
Common mistakes
- Setting Uc only to the nominal phase-to-ground voltage and ignoring the 1.05 harmonic/tolerance factor and steady-state regulation — the arrester runs hot and ages early.
- Ignoring the earth-fault factor on a high-impedance or isolated system: the sound-phase TOV can reach line-to-line voltage and the arrester must be sized to Um, not Um/√3.
- Reading the TOV capability for 1 s when the protection clears in several seconds — Tt drops with duration and the required Ur rises.
- Choosing Ur by Uc alone and forgetting the TOV criterion, or vice versa — Ur must satisfy both max(Ur(Uc), Ur(TOV)).
- Confusing Up (residual at In) with Uc or Ur, then computing the margin against the wrong voltage — the margin is always BIL vs Up.
- Specifying Is below the prospective fault current Ik″, so the arrester cannot fail safely under overstress.
Frequently asked questions
What is the difference between Uc, Ur and Up?
Uc (MCOV) is the maximum continuous power-frequency voltage the arrester withstands indefinitely. Ur is the rated voltage, the 10-second reference used to define the TOV capability, roughly 1.25·Uc. Up is the residual (protective) voltage that appears across the arrester while it discharges the nominal current In — it is the value compared against the equipment BIL.
Why does Uc need the 1.05 factor and the regulation term?
The arrester conducts continuously, even at normal voltage, so it must tolerate the highest steady-state phase-to-ground voltage. The regulation term covers load-rejection/voltage rise, and the 1.05 factor adds margin for harmonics and metering tolerance. Setting Uc to the bare nominal voltage causes excessive leakage current, heating and premature thermal ageing.
How does grounding affect the rated voltage?
On a solidly grounded system the earth-fault factor k is about 1.3–1.4, so the sound-phase overvoltage during a ground fault is modest. On an isolated or resonant-grounded system the fault can persist and the sound phases rise toward the line-to-line voltage (k up to √3 ≈ 1.73), forcing a much higher Ur — the calculator references Uc to Um directly in that sustained-fault case.
Why must the TOV capability be read for the fault duration?
A metal-oxide arrester can absorb a temporary overvoltage only for a limited time before thermal runaway. The capability Tt (per unit of Ur) decreases as the fault lasts longer — about 1.15 at short durations and around 1.04 for very long ones. Reading Tt for too short a time underestimates the required Ur and risks failure during a real, slower-clearing fault.
What protective margin should I target against the BIL?
The protective margin (BIL/Up − 1) should be at least 20% for typical equipment, so the surge is clamped well below the insulation withstand. Cables, gas-insulated switchgear and rotating machines warrant larger margins because their insulation is less self-restoring; long connecting leads to the arrester also erode the effective margin and should be kept short.
Why specify the short-circuit current Is?
If the arrester is overstressed and fails, it must do so safely — venting rather than shattering its porcelain or polymer housing. The rated short-circuit (pressure-relief) current Is must equal or exceed the prospective fault current Ik″ at the installation point so the failure mode stays controlled.
Glossary
- Uc (MCOV)
- Continuous operating voltage: the maximum power-frequency voltage the arrester can withstand continuously without thermal degradation.
- Ur
- Rated voltage: the 10-second power-frequency reference voltage that defines the arrester class and its temporary-overvoltage capability; about 1.25·Uc.
- Up
- Residual or protective voltage: the voltage across the arrester while it discharges the nominal current In; the value compared against the equipment BIL.
- TOV
- Temporary overvoltage: a power-frequency overvoltage of limited duration, typically from a ground fault, that the arrester must ride through without failure.
- BIL / NBI
- Basic lightning impulse insulation level: the standard lightning-impulse withstand voltage of the protected equipment, the reference for the protective margin.
- Earth-fault factor (k)
- Ratio of the highest sound-phase voltage during a ground fault to the nominal phase-to-ground voltage; depends on the system grounding.
- Nominal discharge current (In)
- The standard 8/20 µs current (e.g. 5, 10 or 20 kA) at which the residual voltage Up is defined and the arrester class is rated.